  • Part Number: GXT5-6000IRT5UXLN
  • Dimensions (mm) Unit, W×D×H: 430×630×217
  • Unit Weight (kg): 70.8 74.5
  • Operating Frequency, Nom: 50 or 60 Hz (Factory default is 50 Hz )
  • Maximum Allowable Voltage: 288 VAC
  • AC-AC Efficiency: 94% 94% 94.5% 95%
  • User-configurable Voltage: 200/208/220/230/240 VAC
  • Factory Default Voltage: 230 VAC
  • Warranty: 2 years on part.

Specification

  • Part Number: GXT5-6000IRT5UXLN
  • Dimensions and Weight
  • Dimensions (mm) Unit, W×D×H: 430×630×217
  • Unit Weight (kg): 70.8 74.5
  • Input AC Parameters
  • Operating Frequency, Nom: 50 or 60 Hz (Factory default is 50 Hz )
  • Factory Default Voltage: 230 VAC
  • Operating Voltage Range Without Battery Operation: 176 to 288 VAC (100 to 176 VAC with power derating)
  • Maximum Allowable Voltage: 288 VAC
  • Input Frequency Without Battery Operation: 40 to 70 Hz
  • Output AC Parameters
  • AC-AC Efficiency: 94% 94% 94.5% 95%
  • User-configurable Voltage: 200/208/220/230/240 VAC
  • Factory Default Voltage: 230 VAC
  • Frequency: 50 Hz or 60 Hz, Nominal
  • Waveform: Pure Sinewave
  • Output Power Connection: Output terminal block
  • Main Mode Overload: >150% minimum 200 ms, 125 – 150% for 60 seconds; 105 – 125% for 5 minutes; ≤ 105% continuous
  • Internal Battery
  • Charger Current: 2.25 A (default), maximum 5 A 2.25 A (default), maximum 8 A
  • Type: Valve-regulated, non-spillable, lead acid
  • Qty x V x Rating: 2 x 8 x 12V x 9.0 AH
  • Back-up Time at Full Load: 7 5,5 3,5 2
  • Back-up Time at Half Load: 18,5 14,5 9,5 7
  • Bypass Protection Limits
  • Upper-limit Selections: + 10%, + 15%, + 20%; default + 10%.
  • Lower-limit Selections: - 10%, - 15%, - 20%; default - 15%
  • Disable-bypass Operation: When the input frequency prevents synchronous operation
  • General
  • Operating Temperature, °C: Full power up to 40 ºC (up to 50 ºC with derating)
  • Storage Temperature, °C: - 15 to + 40
  • Relative Humidity: 0 – 95% non-condensing
  • Operating Elevation: Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating
  • Audible Noise: <55 dBA
  • Safety: UL-1788 (Fifth Edition),C-UL listed, IEC 62040-1: 2017 Edition 2.0, EN 62040-1:2008+A1:2013
  • EMI/EMC/C-Tick EMC: IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A), CISPR22 Class A (RFI)
  • ESD: IEC/EN EN61000-4-2, Level 4, Criteria B
  • Radiated Susceptibility: IEC/EN EN61000-4-3, Level 3, Criteria A
  • Electrical Fast Transient: IEC/EN EN61000-4-4, Level 4, Criteria B
  • Surge Immunity: IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B
  • Transportation: ISTA Procedure 1E
  • Warranty: 2 years on part.