APC Smart-UPS RT 5kVA 230V SRTG5KXLI
$2,975.00
- Part Number: SRTG5KXLI
- Lead time: Usually in Stock
- Run time for load: 5000 W
- Min-max: 500-5000 W, 2min 50s
- Max. Capacity Used: 100 %
- Main Input Voltage: 230 V
- Other Input Voltage: 220, 240 V
- Main Output Voltage: 230 V
- Warranty: 3 years repair or replace (excluding battery) and 2 years for battery
Contact for Price & Stock
Delivery 25 Provinces
Official Warranty
100% Genuine Product
Tech Support
Specifications
- Part Number: SRTG5KXLI
- Overview
- Lead time: Usually in Stock
- Main
- Run time for load: 5000 W
- Min-max: 500-5000 W, 2min 50s
- Max. Capacity Used: 100 %
- Main Input Voltage: 230 V
- Other Input Voltage: 220, 240 V
- Main Output Voltage: 230 V
- Other Output Voltage: 220 V, 240 V
- Rated power in W: 5000 W
- Rated power in VA: 5000 VA
- output connection type
- 2 IEC 60320 C13
- 1 IEC 60320 C19
- Output connector type: Hard wire 3-wire (H N + E) 1
- Battery type: Lead-acid battery
- Provided equipment:
- Smart UPS signalling RS-232 cable
- User manual
- USB cable
- General
- Number of power module free slots: 0
- Number of power module filled slots: 0
- Redundant: No
- Physical
- Height: 17.78 cm
- Width: 44 cm
- Depth: 62 cm
- Net weight: 51.9 kg
- Mounting preference: No preference
- Mounting mode: Rack-mounted with kit
- Two post mountable: 0
- USB compatible: No
- Input
- Network frequency: 40...70 Hz auto-sensing
- Number of input connectors: 1 hard wire 3-wire (1P + N + E)
- Input voltage limits: 160...285 V
- Maximum input current: 30 A
- Switching current capacity: 40 A
- Output
- Maximum configurable power in W: 5000 W
- Harmonic distortion: Less than 2 %
- Output frequency: 50/60 Hz +/- 3 Hz sync to mains
- Crest factor: 3 : 1
- UPS type: Double conversion online
- Wave type: Sine wave
- Bypass type: Internal bypass (automatic and manual)
- Full load runtime: 00:03:30 5000 W
- Half load runtime: 00:10:20 2500 W
- Maximum configurable power in VA: 5000 VA
- Conformance
- Product certifications: CE
- Standards
- EN/IEC 62040-1:2019/A11:2021
- EN/IEC 62040-2:2006/AC:2006
- EN/IEC 62040-2:2018
- Environmental
- Ambient air temperature for operation: 0…40 °C
- Relative humidity: 0…95 % non-condensing
- Operating altitude: 0...6600 ft
- Ambient air temperature for storage: -15…45 °C
- Storage Relative Humidity: 0…95 % non-condensing
- Storage altitude: 0.00…15240.00 m
- Acoustic level: 55 dBA
- heat dissipation: 1108.95 Btu/h
- IP degree of protection: IP20
- Batteries & Runtime
- Run Time: View Runtime Graph
- Efficiency: View Efficiency Graph
- Number of battery filled slots: 2
- Number of battery free slots: 0
- Battery recharge time: 4 h
- Number of battery replacement quantity: 2
- Additional information: Configurable for 220 : 230 or 240 nominal output voltage
- Battery voltage: +/- 96 V
- Battery charger power: 239 W rated
- Battery power in VAH: 960 VAh capacity, 960 VAh runtime
- Replacement battery: APCRBC170
- Battery option
- SRTG192XLBP4 1 2651 VAh
- SRTG192XLBP4 2 4424 VAh
- SRTG192XLBP4 3 6314 VAh
- SRTG192XLBP4 4 8118 VAh
- Extended runtime: 1
- Communications & Management
- Preinstalled device: Network management card 3 with environmental monitoring
- Alarm: Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm
- Emergency power off: Yes
- Surge Protection and Filtering
- Surge energy rate: 600 J
- Packing Units
- Unit Type of Package 1: PCE
- Number of Units in Package 1: 1
- Package 1 Height: 27.5 cm
- Package 1 Width: 79 cm
- Package 1 Length: 59 cm
- Package 1 Weight: 59 kg.